Details
SPD Series Split Core CT Bolt-On Type
The SPD Series bolt-on split core current transformer is designed for retrofit metering and monitoring applications where the existing cable or busbar should not be disconnected.
The split-core construction allows installation around existing conductors, making it suitable for panel upgrades, sub-metering, energy monitoring, EMS, BMS, SCADA and IoTWatt 4.0 metering projects.
Product Overview
Split core CTs are useful when energy monitoring or metering points must be added to existing electrical installations. The bolt-on construction provides a secure mechanical assembly around the conductor while avoiding the need to dismantle busbars or disconnect power cables.
The SPD Series is commonly used with multifunction meters, power meters, energy management systems, demand monitoring systems, data loggers, PLCs, BMS, EMS and IoTWatt 4.0 projects.
Why Split Core CTs Matter
In existing panels, downtime and rewiring cost can be the biggest barrier to adding metering points. A split core CT helps reduce installation complexity.
- Retrofit metering
- No cable disconnection
- Reduced shutdown work
- Feeder monitoring
- Machine monitoring
- Sub-metering
- Energy audit points
Applications and Best-Fit Sites
- Energy metering
- Sub-metering
- EMS / BMS / SCADA
- IoTWatt 4.0 projects
- Demand monitoring
- Energy audit measurement
- Tenant metering
- Machine-level monitoring
- Feeder monitoring
- DB / MCC panels
- Busbar applications
- Retrofit panels
Key Features at a Glance
General Specifications
| Parameter | Specification |
|---|---|
| Product Type | Bolt-on split core current transformer. |
| Rated Primary Current | 5A to 5000A, depending on model and CT ratio. |
| Secondary Output | 5A or 1A. |
| Accuracy | 0.5% to 1% from 10% to 150% of full-scale range, depending on model and burden. |
| Rated Test Voltage | 3kV AC for 1 minute. |
| Rated Short-Time Thermal Current | 60In. |
| Rated Dynamic Current | 2.5Ith. |
| Rated Voltage | 0.72kV AC. |
| Operating Temperature | -10掳C to +50掳C. |
| Housing Rating | UL 94V0. |
| Safety Factor | FS 5. |
Model and Dimension Selection
| Model | Outer L | Outer W | Outer H | Window a | Window e | Install M | Install N | CT Ratio | Burden |
|---|---|---|---|---|---|---|---|---|---|
| SPD-XH-30x20 | 90 mm | 40 mm | 110 mm | 20 mm | 30 mm | 49 mm | 52 mm | 100/5 to 400/5 | 1VA to 2.5VA |
| SPD-XH-80x50 | 115 mm | 37 mm | 156 mm | 50 mm | 80 mm | 81 mm | 50 mm | 250/5 to 1000/5 | 1.5VA to 5VA |
| SPD-XH-80x80 | 145 mm | 37 mm | 159 mm | 80 mm | 80 mm | 111 mm | 45 mm | 250/5 to 1000/5 | 1.5VA to 5VA |
| SPD-XH-120x80 | 145 mm | 37 mm | 200 mm | 80 mm | 120 mm | 111 mm | 45 mm | 500/5 to 1500/5 | 2.5VA to 7.5VA |
| SPD-XH-160x80 | 185 mm | 53 mm | 248 mm | 80 mm | 160 mm | 118 mm | 45 mm | 1000/5 to 3000/5 | 10VA to 15VA |
Dimension Reference
Confirm the available panel space, conductor size and mounting clearance before selecting the CT window size. For busbar systems, check both the conductor dimension and the available installation access.
Why Use Bolt-On Split Core CTs?
Installation and Commissioning Notes
Correct CT selection and installation are important for reliable measurement. The CT ratio must match the meter setting, the secondary wiring must be correctly connected, and the CT should be installed in the correct direction where power direction or kW measurement is required.
- Confirm primary current rating
- Confirm 5A or 1A meter input
- Confirm CT ratio setting
- Check burden and cable length
- Install with correct polarity
- Check kW direction
- Check phase matching
- Short CT secondary safely during maintenance
Integration with Energy Monitoring Systems
The SPD Series can be used with compatible power meters, multifunction meters and energy monitoring systems. It is suitable for IoTWatt 4.0 Digital Energy Audit and energy management projects where multiple feeders, machines, DBs or utility sections need to be monitored.
- Multifunction meters
- Power meters
- kWh meters
- RS485 meters
- IoTWatt 4.0 gateways
- Feeder kW / kWh monitoring
- Demand monitoring
- Tenant allocation
- Energy audit measurement
- EECA reporting support
- Savings verification
Recommended CT Selection Checklist
- Confirm conductor / busbar size
- Confirm primary current range
- Confirm CT ratio
- Confirm 5A or 1A secondary
- Confirm connected meter burden
- Confirm cable length burden
- Confirm accuracy class need
- Confirm panel space
- Confirm CT polarity direction
- Confirm phase matching
- Confirm safe access
- Test current and kW reading
SPD Series CT Supply and Energy Monitoring Integration
Saturn Pyro supports SPD Series bolt-on split core CTs for energy metering, sub-metering, EMS, BMS, power monitoring, IoTWatt 4.0 metering points and industrial retrofit projects in Malaysia.